| Input Voltage Range |
94 - 138 |
| Output |
Power: |
Cont.: |
1000 VA |
| Peak |
5000 VA |
| Voltage: |
115 VRMS |
| Frequency: |
57 - 63 Hz |
| Input/Output Isolation |
100 dB (60 Hz) |
| Output Distortion |
0.2% max for up to 10% input harmonic distortion |
| Line Regulation |
±0.025% for ±10% input AC line variation |
| Load Regulation |
±0.025% for no load/full load full current into unity to zero lagging or leading load |
| Temperature coefficient |
0.005% per °C |
| Peak amplitude stability |
±0.01% (cycle to cycle) |
| Amplitude drift |
±0.05% 24 hrs constant line, load and temperature |
| Impulse settling time |
less than 10µsec
|
| Reduces 500 V 10µsec transients by 1000:1 |
| Supplies peak currents 3.5 times RMS rating |